Steve Wilhelm & Associates, Inc.
Home
Contact Us
About Re-Circulating Wells
Contaminants Removed
The Three Technologies We Use
Frequently Asked Questions
Representative Projects
Patents
Recent Developments

Blowerless In-Well Stripping

In-Well Stripping With No Aboveground Blower System

Blowerless In-Well Stripping (BIWS) is a simple patent-pending technology that strips the groundwater with air (or other sparging fluid) in the well, as in traditional in-well stripping.  BIWS uses recirculating wells to accomplish the compression of the air and the stripping of the water.  Recirculating wells enable BIWS to treat large capture widths.

There are two differences between blowerless in-well stripping and traditional in-well stripping:

  • No blower system or other aboveground equipment.  BIWS uses no blower, compressor, or air pump of any kind; unless the off-gas requires treatment, it uses no aboveground equipment other than a control panel.

  • Power consumption is a small fraction of the power consumption of traditional in-well stripping.  In-well stripping wells typically operate with positive displacement (PD) blowers.  In a typical PD blower system operating at 15 psig, more than 75% of the energy used is wasted, largely in generation of useless heat.  In BIWS, compression of the air is isothermal, eliminating the generation of waste heat. 

Typically an in-well stripping system uses 5 to 20 hp per well.  Blowerless in-well stripping uses approximately one fifth the power that a traditional in-well stripping system uses.
The groundwater is circulated several times through the BIWS well and a large treatment zone established around the well, and treated for removal of contaminants (and saturation of the water with oxygen) during each of several passes through the well.

Dissolved volatile (and some semi-volatile) contaminants (e.g., BTEX, MTBE) are removed from the groundwater by the stripping action of the air, which occurs entirely inside the well. 

The entire process is completed belowground, with the only aboveground expression of the system being a small manhole cover and a power pole with a power meter and a small control panel.  BIWS systems can be located virtually anywhere a drill rig can drill a well, even in an active driveway or the middle of a busy street.

While there are numerous possible configurations, each optimized for a different set of geologic conditions, the most basic approach is also the most commonly used.   Figure 1 shows the basic configuration.

  • The BIWS well penetrates to the maximum depth of the dissolved contamination, or to a depth chosen to achieve a desired capture width.  An inlet screen is set at or near the top of the groundwater.

  • The BIWS well incorporates a second screen, an outlet screen, usually at or near the bottom of the well.

  • The inlet portion of the well is separated from the outlet portion by a packer.

  • The water is pumped by a submersible pump (or other means) to a point above the static groundwater level, where its direction reverses and it begins to travel back down the well toward the outlet screen.

  • As the water flows downward, a partial vacuum is formed in the down pipe.

  • At a point along the downward path, a metered amount of air is admitted to the down pipe, where it mixes vigorously and thoroughly with the water.

  • The water and air (bubble) mixture travel downward to the outlet portion of the well.  As the water and air (bubble) mixture descend in the down pipe, the pressure increases to above atmospheric pressure, which increases the saturation concentration of oxygen in water, resulting in the water being oversaturated with oxygen (and other air components) when it reaches the outlet screen.

  • The water and air (bubble) mixture separates below the packer.  The air, laden with stripped contaminants, returns to the surface through a third pipe in the well.  At the surface, the air is either released to the atmosphere or treated for removal of the contaminants.  If the air is treated, it is returned to the well to serve again as the stripping fluid.

  • At the exit screen, higher than normal pressures are formed, resulting in higher head values near the well.

  • The treated water, containing the dissolved oxygen (and other components of air), flows outward from the well and upward under the influence of the vertical gradients created by the extraction process at the top of the well.  Because aquifer materials are typically anisotropic, allowing horizontal flows more readily than vertical flows, the flows tend to be even more outward than upward.

  • A recirculation zone is created that typically returns the majority of the treated water to the inlet screen.  The treated depth, the hydraulic gradient, the hydraulic conductivity, the anisotropy of the aquifer, and the pumping rate largely determine the shape and size of the treatment zone.

  • The water cycles through the treatment zone and the well several times, on average, before escaping down gradient.  On each pass through the well, the water is stripped of contaminants.

  • Unless the off-gas requires treatment, there are no aboveground systems or equipment.  Typically, the only aboveground expression of a BIWS system is a manhole with an adjacent power pole that has a utility meter and a small control panel.

If the off-gas requires treatment, a small vapor-phase carbon treatment system is used.
While the basic configuration and process are straightforward, even for this simplest case there are many considerations in designing and installing Blowerless In-Well Stripping (BIWS) systems.  Well diameter, optimal pumping rate, number of wells and well placement, length of the inlet and outlet screens, special development procedures, controls and instrumentation, in-well plumbing configuration, other pumping methods, constructability, and many other factors must be addressed in developing a complete design.  For more complex or challenging geology, there are additional considerations such as confined aquifer configurations and multiple rows of wells.

The major advantages of Blowerless In-Well Stripping technology are discussed below. 

Blowerless In-Well Stripping

Click to see a larger view

Figure 1 - Blowerless In-Well Stripping - Click to see a larger image   (Patent pending)

 

Major Advantages Of Blowerless In-Well Stripping
With Re-Circulating Wells

No Surface Equipment

  • Constructed entirely belowground, BIWS systems take up no aboveground space.  Unless the off-gas requires treatment, the only above ground equipment is a small control panel that operates the submersible pump.

  • Silent operation.

Faster

  • Faster than air sparging.  Pumping the water in an established treatment cell around the well and treating it on several passes through the well is much more thorough than the largely unknowable treatment process of an air sparging approach. 

  • More vigorous than traditional air sparging or pump-and-treat approaches.  Air sparging flows air through paths of least resistance, often treating only a portion of the water that flows through the treatment zone.  However, re-circulating wells induce vertical gradients to vigorously circulate and treat all of the water in the aquifer multiple times.  While the interaction between the air and water in a traditional air sparging system is not well understood, or subject to modeling or calculation, the exact opposite is true for recirculating wells.  The stripping and aeration processes are thorough and rapid, affecting all of the water in the treatment cell.

Cheaper

  • Lower initial capital costs, lower maintenance costs, and faster cleanups result in lower life-cycle costs. 

  • BIWS wells are typically three-inch PVC construction, not much more expensive than traditional air sparging wells.  But, the equipment in the well costs only a small fraction of the cost of a blower system in an enclosure required by an air sparging approach.

  • Fewer wells.  Well spacing typically 2 to 5 times depth of contamination.  At a site with 50 feet of saturated zone, well spacing can be 200+ feet.

  • Lower energy costs.  Because BIWS involves pumping an incompressible fluid (water instead of air), and because the air is compressed isothermally, energy costs are much lower than for traditional in-well stripping.

More Flexible

  • Large well spacings at many sites allow great flexibility in placing wells.  Placing wells at a gas station site, for example, can be quite flexible.

  • Tolerant of variable geology.  Rather than being impeded by thin silt lenses and discontinuous clay layers as traditional in-well stripping systems can be, re-circulation patterns are enhanced by these typical real-world features.

  • The pumping rate can be adjusted after installation to match actual aquifer response.  Pumping rate can be modified to meet changing conditions during cleanup.

  • Does not affect adjacent plumes.  Because groundwater is not extracted, adjacent plumes are not drawn toward a re-circulating well.  Specific plumes or parts of a plume can be targeted. 

  • Compatible with soil vapor extraction systems.

Regulatory Advantages

  • No extraction of groundwater.  Does not lower groundwater levels beyond the immediate vicinity of the wells.  No re-injection problems.  Eliminates the need for water treatment at the surface, with the attendant routine monitoring and reporting.

 

 
 
Advanced Groundwater Remediation